Voltage Drop Calculator

Estimate voltage drop in copper or aluminium cable for single-phase and three-phase circuits, and the smallest standard size for a target drop.

By Nitin Raturi · Last reviewed

Your circuit

How to use the Voltage Drop Calculator

Estimate the voltage lost along a copper or aluminium cable and the smallest standard size for a target drop.

  1. Choose single-phase or three-phase, and copper or aluminium.
  2. Pick the conductor size and enter the one-way cable length.
  3. Enter the load current, the supply voltage and the conductor temperature.
  4. Set the largest drop you will accept to see the smallest standard size that meets it.

Good to know

  • Reactance is ignored, so long runs of large cables can drop more than shown.
  • A licensed electrician must confirm cable size, current rating and protection.

Resistance only: reactance is not included. Your figures stay in this browser.

Supply type

Supply type

Single-phase uses an outgoing and a return conductor; balanced three-phase uses three line conductors.

How to fill it in

  • Choose single-phase for a normal home circuit or a two-wire DC run (factor 2).
  • Choose three-phase for a balanced three-phase load; the drop is the line-to-line drop (factor √3).

Keep in mind: Unbalanced three-phase loads and neutral currents are not modelled.

Conductor material

Conductor material

Copper or aluminium. Aluminium has higher resistivity, so the same size drops more voltage.

How to fill it in

  • Choose the metal printed on the cable or its datasheet.

Example

The default 25 m run drops 6.6 V in copper and 10.87 V in aluminium.

Conductor size

The nominal cross-section of one conductor in square millimetres, as printed on the cable.

How to fill it in

  • Pick a standard size from 1.5 mm² to 630 mm².
  • For a multi-core cable, use the size of one core, not the total.

Tip: The result also suggests the smallest standard size that meets your target drop.

One-way cable length

The route length from the supply point to the load, in metres, measured one way.

How to fill it in

  • Enter 0.1 to 10,000 m. Do not double it; the calculator adds the return path for single-phase.

Example

Doubling the default run to 50 m doubles the drop to 13.2 V (5.74%).

Load current

The current the circuit carries at its design load, in amperes.

How to fill it in

  • Enter 0.1 to 5,000 A. Use the expected full-load current, not the breaker rating, unless you want a worst case.

Supply voltage

The nominal voltage at the start of the cable: phase-to-neutral for single-phase, line-to-line for three-phase.

How to fill it in

  • Enter 1 to 1,000 V, as stated by your supplier or on the distribution board.

Tip: The percentage drop is measured against this voltage.

Conductor temperature

The temperature of the metal while it carries the load. Warmer conductors have higher resistance.

How to fill it in

  • Enter 0 to 100 °C. The default 70 °C is a cautious working assumption chosen for this tool, not a standard value.
  • If the cable datasheet gives a maximum operating conductor temperature, using it gives a cautious estimate.

Example

The default circuit drops 5.52 V at 20 °C and 6.6 V at 70 °C.

Target maximum drop

The largest drop you will accept, as a percentage of the supply voltage. It drives the suggested size.

How to fill it in

  • Enter 0.1% to 20%.
  • For large commercial buildings, notified ECBC rules (e.g. Tamil Nadu, 2022) set 2% for feeders and 3% for branch circuits at design load.

Keep in mind: This is an estimate for planning. A licensed electrician must check cable size, protection and installation before work.

Voltage drop

6.6 V (2.87%)

A 25 m single-phase run of 2.5 mm² copper at 16 A loses 6.6 V, leaving 223.4 V at the load.

Within your 3% target. Smallest standard size that meets it: 2.5 mm² copper (2.87%).

Voltage at the load
223.4 V
Conductor resistance at 70 °C
8.252 Ω/km
Power lost in the cable
105.6 W
Exact cross-section for your target
2.39 mm²

For large commercial buildings, notified ECBC rules set 2% for feeders and 3% for branch circuits at design load. Other installations may follow different limits.

Resistance only, from resistivity at 70 °C; reactance, power factor, unbalance and harmonics are ignored. Single-phase: 2 × L × I × R.

Safety: this is an estimate, not a design. Cable size also depends on current rating, installation method, grouping, fault protection and local rules. Consult a licensed electrician before buying cable or doing any wiring.

How this calculator works

  1. Step 1Resistivity at temperature0.02063 Ω·mm²/mCopper at 70 °C, from its 20 °C value.
  2. Step 2Resistance per km8.252 Ω/kmResistivity divided by the 2.5 mm² cross-section.
  3. Step 3Drop and percentage6.6 V · 2.87%2 × 25 m × 16 A × resistance per metre.

Current flowing through a cable’s resistance loses some voltage before it reaches the load. The calculator works out that loss from the metal, the cross-section, the length, the current and the conductor temperature.

Resistance rises with temperature. The page uses the linear rule ρ = ρ₂₀ × (1 + α × (T − 20)), with copper and aluminium values from NIST’s wire handbooks.

Single-phase and three-phase

  • Single-phase or two-wire DC2 × L × I × RCurrent goes out on one conductor and back on the other, so the loop is twice the length.
  • Balanced three-phase√3 × L × I × RGives the line-to-line drop for a balanced load at unity power factor.
L is the one-way length in metres, I the current in amperes and R the resistance of one conductor per metre.

Worked example

25 m of 2.5 mm² copper, 16 A, 230 V single-phase
Resistivity at T
ρ = ρ₂₀ × (1 + α × (T − 20))
Voltage drop
Vd = 2 × L × I × ρ ÷ A
Percentage
Vd ÷ supply voltage × 100
  • ρ₂₀Copper resistivity at 20 °C 1/58 = 0.017241 Ω·mm²/m
  • αTemperature coefficient 0.00393 per °C
  • TConductor temperature 70 °C
  1. Resistivity at temperature0.017241 × (1 + 0.00393 × 50)0.020629 Ω·mm²/m
  2. Resistance of one conductor0.020629 ÷ 2.5 × 1,0008.252 Ω/km
  3. Voltage drop2 × 25 × 16 × 0.0082526.6 V
  4. Voltage at the load230 − 6.6223.4 V
  5. Percentage drop6.6 ÷ 230 × 1002.87%

At a 3% target, the exact cross-section needed is 2.39 mm², so 2.5 mm² is the smallest standard size that meets it.

A three-phase example: 100 m of 16 mm² copper carrying 50 A at 400 V drops 11.17 V, or 2.79%.

What changes the drop

  • Copper at 20 °C5.52 V
  • Copper at 70 °C (default)6.6 V
  • Aluminium at 70 °C10.87 V
  • Copper, 50 m instead of 25 m13.2 V
Voltage drop for the default 2.5 mm², 16 A circuit when one thing changes.

Drop grows in direct proportion to length and current, and falls in proportion to cross-section. Aluminium’s higher resistivity and a warmer conductor both raise it.

Choosing a size for a target drop

The suggested size is the smallest standard cross-section whose calculated drop is at or below your target.

The calculator solves the formula for cross-section, then rounds up to the next size in the IS 8130 list, from 1.5 mm² to 630 mm². If even 630 mm² is not enough, it says so.

Voltage drop is only one test. A cable must also carry the current safely for how it is installed, and its protection must clear faults. Those checks are outside this tool.

Which percentage limit applies

Notified ECBC rules set 2% for feeders and 3% for branch circuits, for large commercial buildings only.

The Energy Conservation Building Code, as notified by Tamil Nadu in 2022 (clause 7.2.1.3), caps voltage drop at 2% for feeders and 3% for branch circuits at design load.

Those rules apply to commercial buildings with a connected load of 100 kW or more, or a contract demand of 120 kVA or more. For other installations, ask your electrician which limit applies. The default target here is a planning choice, not a legal limit.

What is not included

  • No reactanceInductive reactance matters for large cables and long runs; it is ignored.
  • No power factor or unbalanceThe load is treated as resistive and, for three-phase, balanced.
  • Nominal cross-sectionReal conductors may have up to the tabulated maximum resistance, a few percent more.

IS 8130 lists the maximum resistance allowed for each conductor size. For 2.5 mm² copper it is 7.41 Ω/km at 20 °C, against 6.897 Ω/km from resistivity. A conforming cable can therefore drop slightly more than shown.

Voltage drop is Ohm's law applied along a cable. Load and resistance come first.

To relate voltage, current and resistance, use the Ohm’s law calculator. For an appliance’s energy use and its cost on your bill, try the electricity calculator.

Common mistakes

  • Mistake: Entering the out-and-back length.

    Instead: Enter the one-way route length; the formula adds the return path.

  • Mistake: Using the breaker rating as the load current.

    Instead: Use the expected design load, or the rating only for a worst case.

  • Mistake: Using line-to-line voltage for a single-phase circuit.

    Instead: Use phase-to-neutral voltage for single-phase and line-to-line for three-phase.

  • Mistake: Choosing a cable on voltage drop alone.

    Instead: Ask a licensed electrician to check current rating and protection too.

Sources and checks

Material constants come from NIST’s copper and aluminium wire tables; sizes from IS 8130; the limit from a state ECBC notification.

Copper uses the International Annealed Copper Standard: 1/58 Ω·mm²/m and 0.00393 per °C at 20 °C. Aluminium uses the EC-H19 (61% IACS) values: 0.028264 Ω·mm²/m and 0.00403 per °C.

An independent script recomputes every golden value differently. It uses conductivity, a Kirchhoff loop for single-phase and complex phasors for three-phase, then finds the size by trying every standard size in turn.

Safety note

Electrical work can cause shock, fire and death. This calculator gives an estimate for planning only. Consult a licensed electrician before choosing cable, changing a circuit or doing any wiring.

Read how we test our calculators, or browse more everyday tools.

Frequently asked questions

How is voltage drop calculated?

Single-phase drop is 2 × length × current × resistance per metre; balanced three-phase uses √3 instead of 2. For 25 m of 2.5 mm² copper at 16 A and 70 °C, that is 6.6 V, or 2.87% of 230 V.

Should I enter the one-way or the round-trip length?

Enter the one-way route length. The single-phase formula already doubles it for the return conductor.

What voltage drop is allowed?

For large commercial buildings, ECBC rules notified by states such as Tamil Nadu set 2% for feeders and 3% for branch circuits at design load. Ask a licensed electrician which limit applies to your installation.

Why does conductor temperature matter?

Metal resistance rises as it warms. Copper resistance rises by about 0.393% for each °C above 20 °C, so a loaded cable drops more than a cold one.

Does the calculator include reactance or power factor?

No. It uses resistance only and assumes a resistive, balanced load. For large cables and long runs, reactance can add to the drop.

Is the suggested cable size safe to install?

Not on its own. Cable size also depends on current rating, installation method, grouping and fault protection. Consult a licensed electrician before buying cable or wiring.